TBS 580  
 Model  TBS 580
 Airflow @ 80 Pa  Industry Standart  10010 m³ / h 5890 cfm
 Cooler Discharge Air Temperature Chart
  Ambient Relative Humidity %
10 20 30 40 50 60 70 80 90
Ambient Dry Bulb

 

10 2.3 3.2 4.2 5.1 6.0 6.8 7.6 8.4 9.2
15 5.6 6.8 8.0 9.1 10.2 11.2 12.2 13.2 14.1
20 8.8 10.3 11.7 13.1 14.4 15.6 16.8 18.0 19.0
25 11.9 13.7 15.4 17.0 18.6 20.0 21.3 22.6 23.8
30 14.8 17.1 19.1 21.0 22.8 24.4 25.9 27.4 28.7
35 17.8 20.4 22.8 25.0 27.0 28.8 30.5 32.1 33.6
40 20.7 23.8 26.6 29.0 31.3 33.3 35.2 36.9 38.5
45 23.5 27.1 30.3 33.1 35.5 37.8 39.8 41.7 43.4
50 26.3 30.5 34.1 37.1 39.9 42.3 44.5 46.5 48.3
 This chart represents approximate air temperatures based on 90% saturation
 efficiency at sea level. From tests carried out to Australian Standart 2913
 Cooling capacity *  kW  16.8
 Power consumption
 (total)
 Watts max  1210
 Current max ( amp )  6.0
 Power supply  Voltage / Phases / Hz  220-240 / 1 / 50
 Controller  Type  Digital
 Fan  Type  Axial
 Dia ( mm )  541
 Motor  Type  PSC
 Speed max ( rpm )  1350 VAR
 Output Watts max  950
 Overload  Auto reset & "one shot"
 fuse
 Enclosure  IP24
 Pump  Type  Centrifugal
CABINET DETAILS
 Motor  Synchronous
 Rating Watts ( input )  25
 Flow rate ( L/ min )  21
 Voltage / Phases / Hz  230 / 1 / 50
 Overload  Auto reset
 Enclosure rating  IPX4
 Cooling pad Chillcel  Size ( mm )  850 x 526 (H) x 120
 (4 pads)
Model A B C D E F G H I* J* K L
TBS 580 835 1150 1150 1080 275 95 82 82 555 555 249 279
 Note: All dimensions are in mm                        Dropper dimensions
 Pad area ( m² )  1.79
 Water  Tank capacity ( L )  23
FAN CURVE

 Inlet ( mm / inches )  12.7 / ½ male BSP
 Drain ( mm / inches )  40 / 1½ male BSP
 Shipping  Dimensions including
 pallet ( mm )
 1150 x 1150 x 902(H)
 Volume ( m³ )  1.19
 Mass ( kg )  68
 Operating ( kg )  91
 Connecting duct
 (raw edged)
 Length x width ( mm )  550 x 550
 *Cooling capacity measured to Australian Standart AS2913-2000, ambient
   of 38° C dry bulb & 21° C wet bulb, with room exit temperature of 27.4° C.
Model Industry STD Rating
m³ / h @ 80 Pa
Motor
W
Certified Air Delivery (m³/h)
( Statik pressure Pa)
0 40 80 120 160
TBS 580 10010 950 11410 10800 10010 9070 7960
   
TBSI 580  
 Model  TBSI 580
 Airflow @ 80 Pa  Industry Standart  10910 m³ / h 6420 cfm
 Cooler Discharge Air Temperature Chart
  Ambient Relative Humidity %
10 20 30 40 50 60 70 80 90
Ambient Dry Bulb
Temperature
°C

 

10 2.2 3.2 4.2 5.1 5.9 6.8 7.6 8.4 9.2
15 5.6 6.8 8.0 9.1 10.2 11.2 12.2 13.2 14.1
20 8.8 10.3 11.7 13.1 14.4 15.6 16.8 18.0 19.0
25 11.8 13.7 15.4 17.0 18.6 20.0 21.3 22.6 23.8
30 14.8 17.1 19.1 21.0 22.8 24.4 25.9 27.4 28.7
35 17.7 20.4 22.8 25.0 27.0 28.8 30.5 32.1 33.6
40 20.7 23.7 26.5 29.0 31.2 33.3 35.2 36.9 38.5
45 23.5 27.1 30.3 33.1 35.5 37.8 39.8 41.7 43.4
50 26.3 30.5 34.1 37.1 39.8 42.2 44.5 46.4 48.3
 This chart represents approximate air temperatures based on cooling
 performance at sea level. From tests carried out to Australian Standart 2913
 Cooling capacity *  kW  18.4
 Power consumption
 (total)
 Watts max  1500
 Current max ( amp )  7.0
 Power supply  Voltage / Phases / Hz  220-240 / 1 / 50
 Controller  Type  Digital
 Fan  Type  Axial
 Dia ( mm )  534
 Motor  Type  Inverter
 Speed max ( rpm )  1700 VAR
 Output Watts max  950
 Overload  Two "one shot" fuse
 Enclosure  IP24
 Pump  Type  Centrifugal
CABINET DETAILS
 Motor  Synchronous
 Rating Watts ( input )  25
 Flow rate ( L/ min )  21
 Voltage / Phases / Hz  230 / 1 / 50
 Overload  Auto reset
 Enclosure rating  IPX4
 Cooling pad Chillcel  Size ( mm )  850 x 526 (H) x 120
 (4 pads)
Model A B C D E F G H I* J* K L
TBSI 580 835 1150 1150 1080 275 95 82 82 555 555 249 279
 Note: All dimensions are in mm                        Dropper dimensions
 Pad area ( m² )  1.79
 Water  Tank capacity ( L )  23
FAN CURVE

 Inlet ( mm / inches )  12.7 / ½ male BSP
 Drain ( mm / inches )  40 / 1½ male BSP
 Shipping  Dimensions including
 pallet ( mm )
 1150 x 1150 x 902(H)
 Volume ( m³ )  1.19
 Mass ( kg )  68
 Operating ( kg )  91
 Connecting duct
 (raw edged)
 Length x width ( mm )  550 x 550
 *Cooling capacity measured to Australian Standart AS2913-2000, ambient
   of 38° C dry bulb & 21° C wet bulb, with room exit temperature of 27.4° C.
Model Industry STD
Rating
m³ / h
@ 80 Pa
Motor
W
Certified Air Delivery (m³/h)
( Statik pressure Pa)
0 40 80 120 160 200 240 280
TBSI
580
10010 950 12240 11660 10910 9860 8820 7700 6160 3600
   
EXS 220  
 Model  EXS 220
 Airflow @ 80 Pa  Industry Standart  9140 m³ / h 5380 cfm
 Cooler Discharge Air Temperature Chart
  Ambient Relative Humidity %
10 20 30 40 50 60 70 80 90
Ambient Dry Bulb
Temperature
°C

 

10 2.3 3.3 4.2 5.1 6.0 6.8 7.7 8.5 9.2
15 5.6 6.9 8.0 9.1 10.2 11.2 12.2 13.2 14.1
20 8.8 10.3 11.8 13.1 14.4 15.6 16.8 18.0 19.0
25 11.9 13.8 15.5 17.1 18.6 20.0 21.4 22.6 23.9
30 14.9 17.2 19.2 21.1 22.8 24.4 26.0 27.4 28.7
35 17.9 20.5 22.9 25.1 27.1 28.9 30.6 32.1 33.6
40 20.8 23.9 26.6 29.1 31.3 33.3 35.2 36.9 38.5
45 23.6 27.2 30.4 33.1 35.6 37.8 39.8 41.7 43.4
50 26.5 30.6 34.2 37.1 39.9 42.3 44.5 46.5 48.3
 This chart represents approximate air temperatures based on cooling
 performance at sea level. From tests carried out to Australian Standart 2913
 Cooling capacity *  kW  15.1
 Power consumption
 (total)
 Watts max  1210
 Current max ( amp )  9.0
 Power supply  Voltage / Phases / Hz  220-240 / 1 / 50
 Controller  Type  Digital
 Fan  Type  Centrifugal
 Dia ( mm )  460 x 380
 Motor  Type  Centrifugal
 Speed max ( rpm )  680 VAR
 Output Watts max  1500
 Overload  Auto reset
 Enclosure  IP2X
 Pump  Type  Centrifugal
CABINET DETAILS
 Motor  Synchronous
 Rating Watts ( input )  25
 Flow rate ( L/ min )  21
 Voltage / Phases / Hz  230 / 1 / 50
 Overload  Auto reset
 Enclosure rating  IPX4
 Cooling pad Chillcel  Size ( mm )  850 x 635 (H) x 120
 (4 pads)
Model A B C D E* F G H I J K L* M N O
EXS
220
860 1160 1160 1108 555 109 38 182 81 274 118 555 834 38 84
 Note: All dimensions are in mm                        Dropper dimensions
 Pad area ( m² )  2.03
 Water  Tank capacity ( L )  11
FAN CURVE

 Inlet ( mm / inches )  12.7 / ½ male BSP
 Drain ( mm / inches )  40 / 1½ male BSP
 Shipping  Dimensions including
 pallet ( mm )
 1160 x 1160 x 955(H)
 Volume ( m³ )  1.29
 Mass ( kg )  87
 Operating ( kg )  94
 Connecting duct
 (raw edged)
 Length x width ( mm )  550 x 550
 *Cooling capacity measured to Australian Standart AS2913-2000, ambient
   of 38° C dry bulb & 21° C wet bulb, with room exit temperature of 27.4° C.
Model Industry STD
Rating
m³ / h
@ 80 Pa
Motor
W
Certified Air Delivery (m³/h)
( Statik pressure Pa)
0 40 80 120 160 200 240
EXS
220
9140 1500 9790 9500 9140 8680 8140 7560 6910
 
 
Web Dizayn Yılmaz EKE

© Copyright 2015 ERKOM Tüm Telif Hakları Saklıdır.

  Merkez  
  Anadolu Bul. 1495. Sokak No:11 İvedik Mah.
06378 - Yenimahalle - Ankara / TÜRKİYE
 
+90 (312) 354 93 00
+90 (312) 354 93 10
  İstanbul Şube  
  Atatürk Mah. Sedef Caddesi 36 Ada Ata 2/2 kat 6
Daire 85,  34750 - Ataşehir - İstanbul / TÜRKİYE
 
+90 (216) 526 18 18
+90 (216) 526 54 54
  Trabzon Şube  
  Sanayi Mahallesi Anadolu Bulvarı No:6/1
61100 - Değirmendere - Trabzon / TÜRKİYE
 
+90 (462) 325 14 24
+90 (462) 325 14 25
erkom@erkom.com.tr